Abstrakt
The article presents results of laboratory tests of point--fixed laminated glass samples with local reinforcement in the form of a steel woven mesh. A total of 16, reference and reinforced samples, were tested. It was found that the reinforcement has a positive effect on the post-breakage capacity of the laminated glass. Local reinforcement in the glass increases the post-breakage strength by 51, 117 and 166% for samples with a reinforcement diameter of 75, 110 and 150 mm, respectively.
| Przetłumaczony tytuł wkładu | Effect of local reinforcement on the post-breakage load capacity of point-fixed laminated glass |
|---|---|
| Język oryginału | polski |
| Strony (od–do) | 14-16 |
| Liczba stron | 3 |
| Czasopismo | Materialy Budowlane |
| Tom | 604 |
| Numer wydania | 12 |
| Identyfikatory DOI | |
| Status publikacji | Opublikowano - 2022 |
Słowa kluczowe
- laminated glass
- post--breakage capacity
- reinforcement point-fixing