The effect of the internal reheat application on the efficiency of the 900 MW ultra-supercritical coal-fired power unit

  • Silesian University of Technology

Wyniki badań: Wkład do czasopismaArtykułrecenzja

3 Cytowania z bazy Scopus

Abstrakt

The paper presents a thermal-economic analysis of a 900 MW coal-fired power unit for ultra-supercritical parameters with internal steam reheat. The subject of the study was the cycle proposed as the "initial thermal cycle structure" during the completion of the project "Advanced Technologies for Energy Generation" with the steam parameters of 650/670 °C /30 MPa. Two configurations of internal reheat were analysed: with a fourand seven-section exchanger. The effect of reheat on the operation of the power unit under a partial load was also analysed, and preliminary calculations of the heat exchange area of the internal reheat were made.