Testing Method for Non-Isothermal Radial Wall Jets from Ceiling Diffusers Used in Building Ventilation

Wyniki badań: Wkład do czasopismaArtykułrecenzja

1 Cytowanie z bazy Scopus

Abstrakt

Diffusers producing radial jets attached to the ceiling are most often used in ventilation and air conditioning systems. In building ventilation, the temperature of the jet supplying the air into the rooms is usually different to the surrounding air temperature. To save energy for air transportation during periods of low heat gains, the air flow should be reduced as low as possible, to about 20% of its nominal value. A significant decrease in the air flow supply in cooling mode may cause cold air dumping and, consequently, increase the risk of local discomfort due to drafts in the occupied zone. In this study, a method for assessing the effect of non-isothermality on the speed distribution of radial wall jets has been developed. The measured terminal speed isolines, W = 0.2 m/s, were compared with the isolines determined for isothermal jets. The test results have shown that, for radial wall jets supplying air at an Archimedes number higher than approximately 50 × 10−4, the risk of jet dumping is significant.

Język oryginałuangielski
Numer artykułu411
CzasopismoEnergies
Tom18
Numer wydania2
Identyfikatory DOI
Status publikacjiOpublikowano - sty 2025

Obszary tematyczne ASJC Scopus

  • Energia odnawialna, zrównoważony rozwój i środowisko
  • Technologia paliwowa
  • Inżynieria (różne)
  • Inżynieria energetyczna i technologia energetyczna
  • Energia (różne)
  • Sterowanie i optymalizacja
  • Inżynieria elektryczna i elektroniczna

Fingerprint

Zanurz się w tematy badawcze publikacji „Testing Method for Non-Isothermal Radial Wall Jets from Ceiling Diffusers Used in Building Ventilation”. Razem tworzą niepowtarzalny odcisk palca.

Cytowanie