Examination of the pneumatic slide valve due to the safety of pneumatic drives

  • Silesian University of Technology

Wyniki badań: Wkład do czasopisma › Artykuł › recenzja

1 Cytowanie z bazy Scopus

Abstrakt

The work deals with safety issues in industrial pneumatics. Standards and directives regarding the safety of pneumatic drives are discussed and tests of the pneumatic slide valve on the created laboratory stand were carried out. During the tests, the influence of valve unused time on its response time was determined. The value of the minimum operating pressure and its influence on the valve switching time were investigated. The obtained results were confronted with the manufacturer's data and analysed for the safety of pneumatic systems. During the tests, a 5/2 solenoid slide valve with a 24V DC coil was used. The aim was to prove the negative impact of the time duration in which the valve was unused on its operation and the time of activation.

Język oryginałuangielski
Strony (od–do)80-85
Liczba stron6
CzasopismoInternational Journal of Modern Manufacturing Technologies
Tom11
Numer wydania2
Status publikacjiOpublikowano - 2019