Abstrakt
The article presents the idea of diagnostic tests of winding-isolation in transformers and in electrical machines. In this method a direct current is feeding the winding, next the current is switched off and the voltage induced in the winding is being recorded. The Oscillations/wave of voltage - depending on the parameters of the winding insulation - can be aperiodic or periodic. Schematic diagrams of electronic switches both single-speed and multi-speed are presented in this article, as well as sample Oscillations/wave of voltage, recorded - after the current is switched off - on oil-transformer with a capacity of 400 kVA and on 800 kVA dry-transformer.
| Przetłumaczony tytuł wkładu | Examination of winding-isolation of transformers with the use of direct current |
|---|---|
| Język oryginału | polski |
| Strony (od–do) | 39-42 |
| Liczba stron | 4 |
| Czasopismo | Przeglad Elektrotechniczny |
| Tom | 91 |
| Numer wydania | 10 |
| Identyfikatory DOI | |
| Status publikacji | Opublikowano - 1 paź 2015 |
Słowa kluczowe
- Diagnostics
- Transformers
- Winding-isolation
- Windings
Obszary tematyczne ASJC Scopus
- Inżynieria elektryczna i elektroniczna
Fingerprint