Przeskocz do nawigacji głównej Przeskocz do wyszukiwania Przeskocz do głównej treści

Badanie izolacji zwojowej transformatorów prądem stałym

  • Upper Silesian Institute of Technology

Wyniki badań: Wkład do czasopismaArtykułrecenzja

Abstrakt

The article presents the idea of diagnostic tests of winding-isolation in transformers and in electrical machines. In this method a direct current is feeding the winding, next the current is switched off and the voltage induced in the winding is being recorded. The Oscillations/wave of voltage - depending on the parameters of the winding insulation - can be aperiodic or periodic. Schematic diagrams of electronic switches both single-speed and multi-speed are presented in this article, as well as sample Oscillations/wave of voltage, recorded - after the current is switched off - on oil-transformer with a capacity of 400 kVA and on 800 kVA dry-transformer.

Przetłumaczony tytuł wkładuExamination of winding-isolation of transformers with the use of direct current
Język oryginałupolski
Strony (od–do)39-42
Liczba stron4
CzasopismoPrzeglad Elektrotechniczny
Tom91
Numer wydania10
Identyfikatory DOI
Status publikacjiOpublikowano - 1 paź 2015

Słowa kluczowe

  • Diagnostics
  • Transformers
  • Winding-isolation
  • Windings

Obszary tematyczne ASJC Scopus

  • Inżynieria elektryczna i elektroniczna

Fingerprint