A control for an unbalanced 3-phase load in UPS systems

  • Silesian University of Technology

Wyniki badań: Wkład do czasopismaArtykułrecenzja

11 Cytowania z bazy Scopus

Abstrakt

Single input single output systems (SISO), which only control the output voltage of a voltage source inverter (VSI) using multi-loop feedback, are not sufficient in the event of a 3-phase unbalanced load. A much better solution is a Multi Input Single Output (MISO) control. In such a case, not only is the output voltage controlled but also the output current and the output filter inductor current. It seems that using a Passivity Based Control (PBC) is just one of the better solutions for a VSI. The paper presents simulations of a modified Improved PBC (IPBC2) using a stationary αβ frame in the event of an unbalanced load in a 3-wire delta load. The simulations were verified using the measurements of a 3-phase inverter experimental model with dynamic balanced and unbalanced loads.

Język oryginałuangielski
Strony (od–do)27-31
Liczba stron5
CzasopismoElektronika ir Elektrotechnika
Tom24
Numer wydania4
Identyfikatory DOI
Status publikacjiOpublikowano - 2018