The Choice of the Control in the Single-Phase Voltage Source Inverters for UPS Systems

Research output: Contribution to journalArticlepeer-review

Abstract

The paper presents four solutions to the voltage source inverter (VSI) control system with existing delays in the measurement channels and the middle switching frequency (25,600 Hz): Single-Input Single-Output Coefficient Diagram Method (SISO-CDM), Multi-Input Multi-Output Passivity-Based Control (MISO-PBC), Multi-Input Multi-Output One-Sample-Ahead Preview Controller (MISO-OSAP), and MISO-OSAP with Luenberger Observer (MISO-OSAP-LO). The theory, including adjustments to controller gains or to the coefficients of the characteristic equation of the closed-loop system, is presented. Simulations of the VSI operation with these control systems for the nonlinear load and the dynamic resistive load (per the requirements of the EN 62040-3 standard) are presented. The SISO-CDM and MISO-PBC are finally selected for experimental verification of the simulations. The results of the tests enable the selection of the control type for a particular VSI design based on its cost and an estimation of the advantages of the more expensive solution. The paper should help in engineering design according to the remarks in the paper.

Original languageEnglish
Article number1548
JournalEnergies
Volume19
Issue number6
DOIs
Publication statusPublished - Mar 2026

Keywords

  • coefficient diagram method
  • deadbeat control
  • Luenberger observer
  • multi-input single-output control
  • one-sample-ahead preview control
  • passivity-based control
  • single-input single-output control
  • voltage source inverter

ASJC Scopus subject areas

  • Renewable Energy, Sustainability and the Environment
  • Fuel Technology
  • Engineering (miscellaneous)
  • Energy Engineering and Power Technology
  • Energy (miscellaneous)
  • Control and Optimization
  • Electrical and Electronic Engineering