Abstract
This paper presents a new fractional-order power system stabilizer, PSS3B_FRAC, developed as a modification of the standard PSS3B stabilizer. Optimization-based procedures are applied to determine stabilizer parameters in single-machine and multi-machine systems. The results demonstrate that introducing fractional-order differentiation improves damping of electromechanical swings while maintaining acceptable voltage regulation. The study is conducted in three stages: (1) single-objective optimization in single-machine systems, (2) single-objective optimization in a 7-machine CIGRE system, and (3) poly-optimization in the same system.
| Original language | English |
|---|---|
| Pages (from-to) | 251-276 |
| Number of pages | 26 |
| Journal | Archives of Control Sciences |
| Volume | 36 |
| Issue number | 2 |
| DOIs | |
| Publication status | Published - 2026 |
Keywords
- electromechanical swings
- fractional-order model
- parameter optimization and poly-optimization
- power system
- power system stabilizers
ASJC Scopus subject areas
- Control and Systems Engineering
- Modeling and Simulation
- Control and Optimization
Fingerprint
Dive into the research topics of 'Poly-optimization of parameters of fractional-order power system stabilizers operating in the power system'. Together they form a unique fingerprint.Cite this
- APA
- Author
- BIBTEX
- Harvard
- Standard
- RIS
- Vancouver