Skip to main navigation Skip to search Skip to main content

Optimization of guide vane positions in bended inflow of mechanical draft wet-cooling tower

  • Silesian University of Technology
  • Projchłod Sp. Z O.o.

Research output: Contribution to journalArticlepeer-review

1 Citation (Scopus)

Abstract

Optimization of vane positions in a mechanical draft wetcooling tower is presented in this paper. The originally installed, equally spaced, vanes produced non-uniform air velocity distribution reducing the performance of the fill of the cooling tower. A 2D CFD model of the tower has been created. The model has then been used to determine the objective function in the optimization procedure. The selected objective function was the standard deviation of the velocity of air entering the fill. The Goal Driven Optimization tools of the ANSYSWorkbench 2.0 have been used for the optimization and the ANSYS Fluent 13.0 as a flow solver. The optimization allowed reduction of the objective function and producing a more uniform air flow.

Original languageEnglish
Pages (from-to)263-272
Number of pages10
JournalArchives of Thermodynamics
Volume32
Issue number3
DOIs
Publication statusPublished - 2011

Keywords

  • Mechanical draft wet-cooling towers
  • Multiphase flow
  • Optimization

ASJC Scopus subject areas

  • General Physics and Astronomy

Fingerprint

Dive into the research topics of 'Optimization of guide vane positions in bended inflow of mechanical draft wet-cooling tower'. Together they form a unique fingerprint.