Abstract

Mathematical models of a generator-transformer unit connected with the power system via a transmission line are presented, which enable the simulation of faults and some emergency conditions, like: loss-of-excitation and out-of-step operations. Current and voltage signals, measured at relaying points of generator-transformer units during these disturbances, are determined. These signals can be used for the transient testing of respective protective relays or schemes.