Abstract
The paper presents parameter estimation of the model of a turbogenerator of rated power PN=50 MW working in a thermal electric plant. The disturbance waveforms measured at a step change of the reference voltage of the generator voltage regulator - for generator parameters in d axis as well as for active and passive load rejection for generator parameters in q axis were the basis for estimation. The problem of measuring the generator power angle as well as processing and filtrating the measurement signals is discussed.
| Translated title of the contribution | Pomiarowa estymacja parametrów modelu generatora synchronicznego pracującego w elektrociepłowni |
|---|---|
| Original language | English |
| Pages (from-to) | 46-49 |
| Number of pages | 4 |
| Journal | Przeglad Elektrotechniczny |
| Volume | 88 |
| Issue number | 9 A |
| Publication status | Published - 2012 |
Keywords
- Genrou model
- Load rejection test
- Parametr estimation
- Synchronous generator
ASJC Scopus subject areas
- Electrical and Electronic Engineering
Fingerprint
Dive into the research topics of 'Measurement parameter estimation of the model of a synchronous generator working in thermal electric power plant'. Together they form a unique fingerprint.Cite this