Skip to main navigation Skip to search Skip to main content

Local balance-based adaptive control in the heat distribution system - Practical validation

Research output: Contribution to journalArticlepeer-review

32 Citations (Scopus)

Abstract

This paper presents the experiences from the practical implementation and the results of the experimental validation of the balance-based adaptive control (B-BAC) methodology in the application to two local control problems in the simple heat distribution system: the control of the outlet temperature for the electric flow heater and the control of a fluid flow process through the equal percentage valve. Evaluation criteria include measure of the control variable performance as well as the manipulated variable action. The results illustrate both the possibility of the practical implementation of the B-BAC methodology and the fact that in some cases this methodology ensures better disturbance rejection with the tracking properties comparable to the conventional PI controller.

Original languageEnglish
Pages (from-to)879-891
Number of pages13
JournalApplied Thermal Engineering
Volume30
Issue number8-9
DOIs
Publication statusPublished - Jun 2010

Keywords

  • Experimental evaluation
  • Heat distribution control
  • Local flow control
  • Local temperature control
  • Nonlinear adaptive model-based control

ASJC Scopus subject areas

  • Energy Engineering and Power Technology
  • Industrial and Manufacturing Engineering

Fingerprint

Dive into the research topics of 'Local balance-based adaptive control in the heat distribution system - Practical validation'. Together they form a unique fingerprint.