Exposure of health care workers to coughed airborne pathogens in a hospital room with overhead mixing ventilation: Impact of ventilation rate and downstream distance from coughing patient

  • Technical University of Denmark

Research output: Contribution to journal › Conference article › peer-review

1 Citation (Scopus)

Abstract

The exposure of medical workers to coughed air by infected patient, positioned at 0.55, 1.1 and 2.8 m (1.8, 3.61 and 9.19 ft) downstream the cough, was studied in a simulated hospital isolation room with two beds. The room was ventilated at three air change rates (3 h-1, 6 h-1 and 12 h-1) by mixing air distribution keeping constant room air temperature at 22° C (71.6° F). Thermal manikin with reali stic body shape and surf ace temperatu re distri bution was used to resemble a doctor. A coughi ng patient (equipped with cough generator) lying in one bed and another patient in the second bed were simulated by two heated dummies with simplified geometry. The cough consisted of 100% CO2. The doctor and the coughing patient were facing each other. The Peak Cough Time was 4 s and remained unchanged regardless of the space ventilation rate, when the doctor was 0.55 m (1.8 ft) downstream from the coughing patient. It increased with the distance. The 12 h-1 led to the highest level of exposure to coughed air for the doctor at the distance of 1.1 m (3.61 ft). Ventilation rates of 12 h -1 (recommended by present hospital standards) resulted in background velocities exceeding 0.5 m/s, 98.43 fpm, suggesting elevated risk from draught for the medical staff.

Original languageEnglish
JournalIAQ Conference
Publication statusPublished - 2011
EventAirborne Infection Control - Ventilation, IAQ, and Energy Conference, IAQ 2010 - Kuala Lumpur, Malaysia
Duration: 10 Nov 2010 → 12 Nov 2010

ASJC Scopus subject areas

  • Building and Construction
  • Environmental Engineering
  • Public Health, Environmental and Occupational Health