TY - GEN
T1 - Exposure of health care workers and occupants to coughed air in a hospital room with displacement air distribution
T2 - 10th International Conference on Healthy Buildings 2012
AU - Popio-Lek, Zbigniew
AU - Bolashikov, Zhecho
AU - Kostadinov, Kamen
AU - Kierat, Wojciech
AU - Melikov, Arsen
PY - 2012
Y1 - 2012
N2 - The exposure of a doctor and a second patient to coughed air by an infected patient was studied in a simulated two-bed hospital patient room ventilated at two air change rates (3 h-1 and 6 h-1). Thermal manikin with realistic body shape and surface temperature distribution was used as the doctor standing 0.55, 1.1 or 2.8 m downstream the cough. A coughing thermal dummy, lying in one bed and a second thermal manikin in the other bed (1.3 m away), were used as the "sick" and the "exposed" patients. The cough consisted of 100% CO2. The doctor and the coughing patient faced each other. The highest Peak Concentration Level (PCL) for the doctor was at 6 h-1, suggesting that the risk of airborne cross infection may increase when ventilation rate is increased. Displacement air distribution does not reduce the risk from crossinfection.
AB - The exposure of a doctor and a second patient to coughed air by an infected patient was studied in a simulated two-bed hospital patient room ventilated at two air change rates (3 h-1 and 6 h-1). Thermal manikin with realistic body shape and surface temperature distribution was used as the doctor standing 0.55, 1.1 or 2.8 m downstream the cough. A coughing thermal dummy, lying in one bed and a second thermal manikin in the other bed (1.3 m away), were used as the "sick" and the "exposed" patients. The cough consisted of 100% CO2. The doctor and the coughing patient faced each other. The highest Peak Concentration Level (PCL) for the doctor was at 6 h-1, suggesting that the risk of airborne cross infection may increase when ventilation rate is increased. Displacement air distribution does not reduce the risk from crossinfection.
KW - Air distribution
KW - Airborne cross infection
KW - Coughing thermal manikin
KW - Physical measurements
UR - https://www.scopus.com/pages/publications/84883322156
M3 - Conference contribution
AN - SCOPUS:84883322156
SN - 9781627480758
T3 - 10th International Conference on Healthy Buildings 2012
SP - 1292
EP - 1297
BT - 10th International Conference on Healthy Buildings 2012
Y2 - 8 July 2012 through 12 July 2012
ER -