Abstract
Four com. membrane water treatment plants were analyzed for their operability and reliability. The reverse osmosis-based plants for purifn. of drinking water consists of coagulation with FeCl3, flocculation, neutralization with HCl, two-stage filtration, two-stage permeation and disinfection with ClO2 (capacity 40 m3/h). Another plant for mine water treatment based on reverse osmosis yields drinking water with a capacity 800 m3/d. The microfiltration-based water treatment plant is used for purifn. of mine water used for techn. purposes. It includes oxidn. of crude water with KMnO4, disinfection with NaOCl and cleaning the capillary membranes with an air stream. Another plant uses microfiltration for purifn. of river water delivered as drinking water after addn. disinfection with NaOCl.
| Translated title of the contribution | Analysis of the reliability of the water treatment plants based on membrane technologies |
|---|---|
| Original language | Polish |
| Pages (from-to) | 485-488 |
| Number of pages | 4 |
| Journal | Przemysl Chemiczny |
| Volume | 87 |
| Issue number | 5 |
| Publication status | Published - 2008 |