Abstract
Single input single output systems (SISO), which only control the output voltage of a voltage source inverter (VSI) using multi-loop feedback, are not sufficient in the event of a 3-phase unbalanced load. A much better solution is a Multi Input Single Output (MISO) control. In such a case, not only is the output voltage controlled but also the output current and the output filter inductor current. It seems that using a Passivity Based Control (PBC) is just one of the better solutions for a VSI. The paper presents simulations of a modified Improved PBC (IPBC2) using a stationary αβ frame in the event of an unbalanced load in a 3-wire delta load. The simulations were verified using the measurements of a 3-phase inverter experimental model with dynamic balanced and unbalanced loads.
| Original language | English |
|---|---|
| Pages (from-to) | 27-31 |
| Number of pages | 5 |
| Journal | Elektronika ir Elektrotechnika |
| Volume | 24 |
| Issue number | 4 |
| DOIs | |
| Publication status | Published - 2018 |
Keywords
- Multi input single output control
- Passivity based control
- Unbalanced load
- Voltage source inverter
ASJC Scopus subject areas
- Electrical and Electronic Engineering
Fingerprint
Dive into the research topics of 'A control for an unbalanced 3-phase load in UPS systems'. Together they form a unique fingerprint.Cite this