Skip to main navigation Skip to search Skip to main content

A control for an unbalanced 3-phase load in UPS systems

  • Silesian University of Technology

Research output: Contribution to journalArticlepeer-review

11 Citations (Scopus)

Abstract

Single input single output systems (SISO), which only control the output voltage of a voltage source inverter (VSI) using multi-loop feedback, are not sufficient in the event of a 3-phase unbalanced load. A much better solution is a Multi Input Single Output (MISO) control. In such a case, not only is the output voltage controlled but also the output current and the output filter inductor current. It seems that using a Passivity Based Control (PBC) is just one of the better solutions for a VSI. The paper presents simulations of a modified Improved PBC (IPBC2) using a stationary αβ frame in the event of an unbalanced load in a 3-wire delta load. The simulations were verified using the measurements of a 3-phase inverter experimental model with dynamic balanced and unbalanced loads.

Original languageEnglish
Pages (from-to)27-31
Number of pages5
JournalElektronika ir Elektrotechnika
Volume24
Issue number4
DOIs
Publication statusPublished - 2018

Keywords

  • Multi input single output control
  • Passivity based control
  • Unbalanced load
  • Voltage source inverter

ASJC Scopus subject areas

  • Electrical and Electronic Engineering

Fingerprint

Dive into the research topics of 'A control for an unbalanced 3-phase load in UPS systems'. Together they form a unique fingerprint.

Cite this